WANG Weibo, ZHANG Shunda, ZHU Qimin. Cause analysis and improvement of surfacing defects of nuclear grade 1 globe valve. [J]. 51(3):95-99(2021)
DOI:
WANG Weibo, ZHANG Shunda, ZHU Qimin. Cause analysis and improvement of surfacing defects of nuclear grade 1 globe valve. [J]. 51(3):95-99(2021) DOI: 10.7512/j.issn.1001-2303.2021.03.17.
Cause analysis and improvement of surfacing defects of nuclear grade 1 globe valve
A nuclear grade 1 globe valve has internal leakage in nuclear power plant,and further inspection reveals that the cemented carbide(iron base) welded on the sealing surface of the valve has cracks,leading to internal leakage of the valve.By analyzing the causes of the cracks,the procedure and welding process control are improved,and the crack problem of the iron base surfacing are basically solved. The references are provided for the treatment of the sealing surface defects of similar nuclear grade valves in subsequent nuclear power plants.