Failure analysis of bellows in GIS equipment of 750 kV substation
Vol. 49, Issue 12, Pages: 22-28(2019)
Published:2019
DOI:
稿件说明:
移动端阅览
DOI:
LUO Hongjian, LI Zhenggang, ZHANG Jie, et al. Failure analysis of bellows in GIS equipment of 750 kV substation[J]. Eletric Welding Machine2019, 49(12): 22-28.DOI:
Failure analysis of bellows in GIS equipment of 750 kV substation
The normal operation of bellows in GIS equipment is related to the safety and stability of the substations. The bellows and welds where occurs leakage in GIS equipment of a 750 kV substation are analyzed through macro-inspection
fracture analysis
micro-morphology analysis and chemical composition analysis. And the stress distribution of defective bellows was calculated by finite element method
and the failure reasons of bellows with leakage were analyzed. The results show that stress corrosion is the main reason of leakage and perforation of bellows. Meanwhile
the strength of the joint of bellows decreases due to welding defects
resulting in local crack of the weld and leakage. Therefore
in the production process of bellows
it is necessary to improve the welding procedure and strengthen the non-destructive testing of welding product quality
so as to prevent the introduction of pollutants and effectively avoid bellows failure.